| Sign In | Join Free | My chinacomputerparts.com |
|
| Categories | 3 Phase UPS |
|---|---|
| Brand Name: | RSUN or OEM service |
| Model Number: | DT33-160K |
| Place of Origin: | China |
| MOQ: | 1 |
| Price: | Negotiation |
| Payment Terms: | L/C,T/T |
| Supply Ability: | 10,000PCS per month |
| Delivery Time: | 25 working days |
| Packaging Details: | Wooden box |
| Type: | Three Phase UPS |
| Capacity: | 160KVA 160KW |
| Input Voltage: | 304Vac ~ 478Vac (line voltage) full load; 304Vac ~ 228Vac (line voltage) load |
| Output Voltage: | 380/400/415Vac (3phase+N) |
| Power factor: | 1.0 |
| THD: | ≤2% (100% linear load), ≤4% (nonlinear load) |
| Efficiency: | Inverter mode ≥95%, ECO Mode ≥99% |
| Battery: | 32; 30 ~ 44(±15~±22)(settable) |
| Net Weight: | 360KG |
| Company Info. |
| Rsun Power Technology Co.,Ltd |
| Verified Supplier |
| View Contact Details |
| Product List |
UPS 160kva 160KW Three Phases Online UPS 30 - 44 Units Battery For Industrial UPS LCD
DESCRIPTIONS:
The RSUN DT33 Series is a high-capacity UPS featuring true double-conversion with three-phase input and output, tailored for demanding power environments. Equipped with advanced power factor correction (PFC) reaching 0.99, it enhances energy efficiency and eases grid load. Its compact, high-density design suits space-constrained setups. Precision digital controls deliver stable operation with comprehensive self-monitoring and fault diagnostics. The DT33 safeguards critical equipment by mitigating a broad spectrum of power disturbances, voltage dips, surges, transients, harmonic distortion, frequency variations, and more ensuring uninterrupted, clean power delivery.
SPECIFICATIONS:
| Model | DT33-10K | DT33-20K | DT33-30K | DT33-40K | DT33-50K | DT33-60K | DT33-80K | DT33-100K | DT33-120K | DT33-160K | DT33-200K | ||
| Capacity | 10kVA | 20kVA | 30kVA | 40kVA | 50kVA | 60kVA | 80kVA | 100kVA | 120kVA | 160kVA | 200kVA | ||
| Input | |||||||||||||
| Rated Voltage | 380Vac (3 phase+N) | ||||||||||||
| Voltage Range | 304Vac ~ 478Vac (line voltage) full load; 304Vac ~ 228Vac (line voltage) load derated linearly from100% to 80% | ||||||||||||
| Frequency Range | 40Hz ~ 70 Hz | ||||||||||||
| Power Factor | ≥ 0.99@100% load;≥ 0.98@50% load | ||||||||||||
| THDi | <3% (100% linear load) ; <5% (100%nonlinear load) | ||||||||||||
| Output | |||||||||||||
| Output Voltage | 380/400/415Vac (3phase+N); | ||||||||||||
| Voltage Accuracy | ±1%@balanced load;±5%@unbalanced | ||||||||||||
| THDu | ≤2% (100% linear load);≤4% (nonlinear load) | ||||||||||||
| Power Factor | 0.9 (1 optional) | ||||||||||||
| Frequency Range | ±2Hz(settable);±0.5Hz,±1Hz,±3Hz(settable) (Synchronizing Range) | ||||||||||||
| Frequency Range | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz (Battery Mode) | ||||||||||||
| Overload | < 105%, long run; < 110%, 60 min; 110~125% rated load, load 10 min; >125~150% rated load, load1 min; >150%, 200ms | ||||||||||||
| Crest Factor | 3:1 (maximum) | ||||||||||||
| Switching Time | 0 ms (Main power Battery) | ||||||||||||
| 1 ms (phase lock failure, <2ms interrupt occurs) (Inverter Bypass) | |||||||||||||
| < 2 ms (Inverter ECO) | |||||||||||||
| Efficiency | |||||||||||||
| Inverter Mode | ≥95% | ||||||||||||
| ECO Mode | ≥99% | ||||||||||||
| Battery | |||||||||||||
| Number | Long backup | 32; 30 ~ 44(±15~±22)(settable) | |||||||||||
| Standard backup | (30~60)x7AH/9AH | (60~80)x7AH/9AH | NA | ||||||||||
| Charging Current | Capacity* 15%/N/12(N=±15-22) | ||||||||||||
| Charging Voltage | ± 13.65Vdc * N ± 1%(N=±15-22) | ||||||||||||
| Physical | |||||||||||||
| Long backup | Size (mm) | 280 x 685 x 725 | 425 x 780 x 1200 | 600 x 800 x 1600 | 600 x 960 x 1600 | 600 x 1010 x 2000 | |||||||
| Net Weight(kg) | 45 | 108 | 230 | 310 | 360 | 460 | |||||||
| Standard backup | Size WxDxH(mm) | 400 x 685 x 1000 | 425 x 780 x 1580 | NA | |||||||||
| Net Weight(kg) | 62 (w/o battery) | 135 (w/o battery) | NA | ||||||||||
| Environment | |||||||||||||
| Working Temperature | 0 ~ 40°C battery life will be shorten when temperature > 25°C | ||||||||||||
| Relative Humidity | 0~95% no condensation | ||||||||||||
| Altitude | 1000 meters no derate, > 1000 meters derating 1% for every 100 meters rise | ||||||||||||
| Noise | ≤ 60dB (A)@ 1 meter | ||||||||||||
| Management | |||||||||||||
| Intelligent RS232/RS485 | Support Windows® 2000/2003/XP/Vista/2008,Windows® 7/8/10,Linux and MAC | ||||||||||||
| Optional | SNMP / Dry contact | ||||||||||||
Q1: Can I place a sample order for the UPS?
A: Absolutely. We encourage sample orders for quality verification,
and mixed model samples are also accepted.
Q2: What is the lead time for samples and bulk orders?
A: Sample preparation usually takes 5 - 7 days. Mass production
requires approximately 25 business days.
Q3: Do you have a minimum order quantity (MOQ) for UPS?
A: We have a low MOQ policy. You can order as few as one unit for
sample testing.
Q4: What shipping methods do you offer and what is the typical
delivery time?
A: Shipments are available via sea freight, DHL, FedEx, and other
couriers. Delivery time depends on the chosen method and
destination.
Q5: How do I place an order for the UPS?
A: Please share your specifications or application details first.
We will provide a quotation based on your needs. Once the sample is
approved and deposit received, production will begin.
Q6: Can I have my company logo printed on the UPS?
A: Yes, OEM logo printing is available. Please notify us before
production starts.
Q7: What warranty do you provide for the UPS?
A: Our products come with a 3-year warranty covering manufacturing
defects and product reliability.
|