| Sign In | Join Free | My chinacomputerparts.com |
|
| Categories | Air to Water Heat Pump |
|---|---|
| Brand Name: | Deakonet |
| Model Number: | 26/37/47/53/74/90/97/145/162/183kW Models |
| Certification: | CE |
| Place of Origin: | China |
| MOQ: | 1 |
| Payment Terms: | ,L/C,T/T |
| Supply Ability: | 5,000 units/Year |
| Delivery Time: | 20-25 Working Days |
| Packaging Details: | Plywood box |
| COP: | 4.6 |
| Compressor: | Copeland EVI Scroll Compressor |
| Refrigerant: | R410A |
| Condenser: | Coaxial Tube Heat Exchanger |
| Fan Motor: | AC |
| Control: | WIFI +APP +4.3/5 Inch Touch Screen Panel |
| Function: | Hot Water+Room Heating/Cooling |
| Applicable Ambient Temperature: | -35℃ |
| Company Info. |
| FOSHAN JUYANG NEW ENERGY CO LTD |
| View Contact Details |
| Product List |
C2 Pro Dual Source Heat Pump
JUYANG NEW ENERGY has developed a dual-source (air + solar) EVI
commercial heat pump that efficiently combines air energy and solar
energy to provide heating, cooling, and hot water
By utilizing Enhanced Vapor Injection (EVI) technology, the heat pump ensures high performance even in extremely low temperatures, making it ideal for various commercial applications. The system maximizes energy savings and reduces operational costs by intelligently switching between air and solar energy sources based on real-time conditions.

Multiple Applications

-Heating: Air source heat pumps extract heat from the outside air and use it for indoor heating. They are suitable for various heating methods, including underfloor heating, radiators, and fan coil units.
-Cooling: In the summer, air source heat pumps can operate in reverse to transfer heat from indoors to the outside, functioning as an air conditioner to provide a cool and comfortable indoor environment.
-Hot Water Supply: Air source heat pumps can heat water for domestic use, such as bathing, laundry, and kitchen needs.
Advantages of the C2 Series
Stable Performance in Low Temperatures: The C2 PRO features an
added solar panel heat exchanger with control valves, enabling the
system to operate in environments with temperatures as low as -35°C.
Environmentally Friendly: By integrating renewable energy sources
like solar energy and utilizing Eco- friendly refrigerant , the
heat pump reduces carbon emissions.






Line-Up
Model | KLR 425C | KLR 850C | KLR 1275C | KLR 1535C | KLR 1700C | KLR 2125C | KLR 3180C | KLR 3400C | KLR 4250C | KLR 5100C | |
Performance at 7°C ambient temperature, with water inlet/outlet temperatures of 30/35°C. | Heating capacity KW | 29 | 41 | 53 | 60 | 84 | 97 | 110 | 161 | 184 | 207 |
Input power KW | 6.3 | 9.0 | 11.7 | 13.1 | 18.3 | 21.1 | 24.2 | 35.2 | 40.3 | 45.5 | |
COP | 4.58 | 4.57 | 4.54 | 4.57 | 4.58 | 4.59 | 4.55 | 4.58 | 4.57 | 4.55 | |
Operating current | A | 9.6 | 13.6 | 17.7 | 19.9 | 27.9 | 32.1 | 36.7 | 53.4 | 61.2 | 69.1 |
Maximum outlet water temperature | ℃ | 60 | |||||||||
Applicable ambient temperature | ℃ | -35~43 | |||||||||
Compressor | Type | Scroll | |||||||||
Fan motor | Type | AC | |||||||||
Condenser | Type | High efficiency tank heat exchanger | |||||||||
Number of Compatible Solar Panels | Pcs | 2 | 2 | 4 | 4 | 6 | 6 | 6 | 8 | 8 | 8 |
Circulating pump (Optional) | Water flow (m3/h) | 5.0 | 7.0 | 9.1 | 10.3 | 14.4 | 16.7 | 18.9 | 27.7 | 31.6 | 35.6 |
Pump head (m) | 10 | 20 | 25 | 25 | 30 | 30 | 30 | 20 | 20 | 30 | |
Input power (KW) | 0.8 | 1.2 | 1.5 | 2 | 3 | 3 | 3 | 5.5 | 7.5 | 9 | |
Water connection size | Inch | 1.25 | 1.5 | 2 | 2 | 2 | 2 | 2.5 | 2.5 | 2.5 | 2.5 |
Refrigerant | Type | R410A | |||||||||
Max exhaust pressure | Mpa | 4.2 | |||||||||
Dimensions | Length (mm) | 780 | 1400 | 1500 | 1500 | 2000 | 2000 | 2000 | 2450 | 2450 | 2450 |
Width (mm) | 780 | 750 | 800 | 800 | 1100 | 1100 | 1100 | 1300 | 1300 | 1300 | |
Height(mm) | 1075 | 1450 | 1550 | 1550 | 1960 | 1960 | 2060 | 2260 | 2260 | 2260 | |
Power supply | Phase/V/Hz | 3/380/50 | |||||||||
Waterproof | Grade | IPX4 | |||||||||
Anti electric shock | Grade | I | |||||||||
Operating noise | db(A) | 60 | 60 | 65 | 67 | 70 | 75 | 79 | 75 | 78 | 78 |
Weight of heat pump | Kg | 148 | 296 | 327 | 390 | 530.5 | 586.5 | 625.5 | 1568 | 1710 | 1780 |

|