| Categories | Air Cooled Screw Chiller |
|---|---|
| Brand Name: | SZAGS |
| Model Number: | AGS-120ASH |
| Certification: | ISO9001, CE |
| Place of Origin: | China |
| MOQ: | 1 |
| Payment Terms: | L/C, T/T |
| Supply Ability: | 100 units per month |
| Delivery Time: | 20-30 days |
| Packaging Details: | plywood case |
| Compressor Type: | Screw |
| Refrigerant Name: | R22/R407C/R410A/R134A |
| Compressor Quantity: | 1 |
| Cooling Capacity: | 382.8kw |
| Application: | Industrial cooling |
| Cooling Mode: | Air cooling |
| Cooling Method: | Air-cooled |
| Cooling Media: | R22/R407/R134 |
| Compressor Control: | 25-50-75-100% |
| Compressor Range Adjust: | 25-50-75-100% |
| Electrical Components: | Schneider |
| Evaporator Type: | Shell and tube |
| Energy Control: | 25-50-75-100% |
| Company Info. |
| Shenzhen Anges Machinery Co., Ltd |
| Verified Supplier |
| View Contact Details |
| Product List |

Technical Parameter of AGS-120ADH Air Cooled Screw Type Chiller
Model Parameter | AGS-120ADH | |
| nominal cooling capacity | kcal/h | 329208 |
| kw | 382.8 | |
| input power | kw | 113 |
| max running current | A | 256.4 |
| power supply | 3PH~380V 50HZ | |
| refrigerant | type | R22 |
| refrigerating circuit | 2 | |
| type of control | thermostatic expansion valve | |
| compressor | type | semi-hermetic screw |
| quantity | 2 | |
| start-up mode | Y-△ | |
| capacity control | 0-25-50-75-100 | |
| evaporator | type | shell and tube |
| quantity | 1 | |
| chilled fluid flow (m3/h) | 65.8 | |
| inlet and outlet pipe diameter (inch) | 4 | |
| condenser | type | air cooled type finned copper tube |
| cooling air flow(m3/h) | 122000 | |
| power(kw) | 6 | |
| safety protection | compressor over temperature, unit overload, high and low pressure, flow switch, phase sequence, phase-missing, antifreezing | |
| net weight | kg | 3850 |
| running weight | kg | 4120 |
Note: 1. Nominal cooling capacity is according to:
Inlet chilled fluid temperature: 17℃
Outlet chilled fluid temperature: 12℃
Inlet cooling air temperature: 30℃
Outlet cooling air temperature: 35℃
2. Working Range:
The temperature range of chilled fluid is from 5℃ to 30℃;
Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.
Temperature difference between inlet and outlet cooling air is from 8℃ to 12℃.
The machine can be used while the ambient temperature is below 38℃.