Sign In | Join Free | My chinacomputerparts.com
chinacomputerparts.com
Products
Search by Category
Home > Temperature Instruments >

Comprehensive Electrical Power Quality Analyzer Rechargeable With 4 Channel Current

Categories Power Quality Analyzer
Brand Name: HAOMAI
Model Number: PQA-500
Certification: ISO9001:2015
Place of Origin: China
MOQ: 1 set
Price: negotiation
Payment Terms: T/T
Supply Ability: 400 sets per month
Delivery Time: 5-10 working days
Packaging Details: Transport Bag + Carton
Product name: PQ Analyzer, PQ Tester
Number of channels: 4U+4I
True RMS phase-to phase voltage: 1.0V-2000V
DC voltage: 1.0V-1000V
True RMS current: 10mA-1000A
Frequency: 40Hz-70Hz
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

Comprehensive Electrical Power Quality Analyzer Rechargeable With 4 Channel Current

Power Quality Analyzer


Model: PQA-500

Power Quality Analyzer PQA-500 is a comprehensive test instrument developed by HAOMAI ELECTRIC and specially designed for field test of three phases, multi-functional and intelligent, concise man-machine operation. It is easy to use, large LCD screen display, high resolution, interface in both Chinese and English, shock-proof shell structure and so on. It can simultaneously measure the 4-channel current (ABC three phase and neutral wire cur-rent), 4-channel voltage (ABC three-phase voltage and neutral line voltage to ground), the peak value of current voltage, maximum/minimum value over a period, three-phase imbalance factor, short-time voltage flicker, transformer K factor, active power, reactive power, apparent power, power factor and displacement power factor, active power, reactive power, apparent power, total harmonic distortion and harmonic etc.; display real-time waveform, harmonic ratio bar charts of current voltage; dynamically capture instantaneous change of voltage current, monitoring starting current, monitoring the power parameters and generate the alarm list, generate the trend chart for a long time record test data.


Technical Data

Power supplyRechargeable lithium-ion battery packs 9.6V, backup charger.
Battery indicatorBattery symbol shows dump energy. When the voltage is too low, automatic shutdown after the 1 minute.
Power consumptionCurrent consumption of normal test 490 mA, continuous working for 8 hours.
Display modeLCD color screen, 640dots×480dots, 5.6 inches, display domain: 116mm×88mm.
Size of clamp

HM-008B small sharp current clamp: 7.5mm×13mm;

HM-040B circle current clamp: 35mm×40mm;

HM-068B circle current clamp: 68mm×68mm.

HM-300F Flexible Coil Current Sensor (with Integrator) : Ф300mm

Instrument dimensionsL×W×H: 240mm×170mm×68 mm.
Number of channels4U/4I.
Phase-to phase voltage1.0V~2000V.
Phase-to-neutral voltage1.0V~1000V.
Current

HM-008B current clamp: 10mA~10.0A;

HM-040B current clamp: 0.10A~100A;

HM-068B current clamp: 1.0A~1000A;

HM-300F Flexible Coil Current Sensor (with Integrator) : 10A ~ 3000A

Frequency40Hz~70Hz.
Parameters of electricityW, VA, Var, PF, DPF, cosφ, tanφ.
Energy parametersWh, Varh, Vah.
HarmonicOrder 0~50.
Total harmonic distortionOrder 0~50, each phase.
Expert modeYes
Number of Transient records150 sets
Voltage flickerYes
Starting current modeYes, 100 seconds.
3 phases unbalanceYes
Record300 days(simultaneous recording 20 parameters, record one point every 5 seconds).
Min/Max recorded valueMeasurement of maximum and minimum values over a period of time.
Alarm40 different types of parameter selections, 12,800 sets alarm logs.
PeakYes
Phasor diagram displayAutomatically.
Capacity of snapshots60
Menu languageEnglish/Chinese.
CommunicationUSB.
Automatic switching offWhen an alarm campaign is initiated or a search for transients, an inrush current capture, or a trend recording is pending or in progress, the device is not automatic switching off.
In other test mode, 15 minutes without keystrokes, automatic shutdown after prompt 1 minute.
Backlight functionYes, suitable for use at night and dark place.
WeightHost: 1.6kg (with battery).
HM-008B small sharp current clamp: 170g×4;
HM-040B circle current clamp: 190g×4;
HM-068B circle current clamp: 510g×4;
HM-300F Flexible Coil Current Sensor (with Integrator) : 330g×4;
Test wires and power adapter: 900g;
Total weight: about 9.2kg (with packaging).
Length of voltage test wire3m
Length of current sensor wire2m
Working temperature and humidity-10°C~40°C; below 80%Rh.
Storage temperature and humidity-10°C~60°C; below 70%Rh.
Input impedanceInput impedance of test voltage: 1MΩ.
Withstand voltageWithstand 3700V/50Hz sinusoidal AC voltage for 1 minute between instrument wiring and shell.
InsulationBetween instrument wiring and shell ≥10MΩ.
StructureDouble insulation, with insulation vibration-proof sheath.
Safely rulesIEC 61010 1000V Cat III / 600V CAT IV, IEC61010-031, IEC61326, Pollution degree: 2.

Measuring Accuracy of PQA-500(current clamp excluded)

MeasurementRangeDisplay resolutionThe maximum error in the range of the reference
Frequency40Hz~70Hz0.01Hz±(0.03)Hz
True RMS phase-to-neutral voltage1.0V~ 1000VMin resolution 0.1V±(0.5%+5dgt)
True RMS phase-to phase voltage1.0V~ 2000VMin resolution 0.1V±(0.5%+5dgt)
DC voltage1.0V~ 1000VMin resolution 0.1V±(1.0%+5dgt)
True RMS current10mA~ 1000AMin resolution 1mA±(0.5%+5dgt)
Peak of phase-to-neutral voltage1.0V~ 1414VMin resolution 0.1V±(1.0%+5dgt)
Peak of phase-to-phase voltage1.0V~ 2828VMin resolution 0.1V±(1.0%+5dgt)
Current peak10mA~ 1414AMin resolution 1mA±(1.0%+5dgt)
Peak factor1.00~ 3.990.01±(1%+2dgt)
4.00~ 9.990.01±(5%+2dgt)
Active power0.000W~ 9999.9kWMin resolution 0.001W

±(1%+3dgt)

Cosφ≥0.8

±(1.5%+10dgt)

0.2≤Cosφ<0.8

Reactive power, inductive or capacitive

0.000VAR~

9999.9kVAR

Min resolution 0.001VAR

±(1%+3dgt)

Sinφ≥0.5

±(1.5%+10dgt)

0.2≤Sinφ<0.5

Apparent power

0.000VA~

9999.9kVA

Min resolution 0.001VA±(1%+3dgt)
Power factor-1.000~ 1.0000.001

±(1.5%+3dgt)

Cosφ≥0.5

±(1.5%+10dgt)

0.2≤Cosφ<0.5

Active energy0.000Wh~ 9999.9MWhMin resolution 0.001Wh

±(1%+3dgt)

Cosφ≥0.8

±(1.5%+10dgt)

0.2≤Cosφ<0.8

Reactive energy, inductive or capacitive

0.000VARh~

9999.9MVARh

Min resolution 0.001VARh

±(1%+3dgt)

Sinφ≥0.5

±(1.5%+10dgt)

0.2≤Sinφ<0.5

Apparent energy

0.000VAh~

9999.9MVAh

Min resolution 0.001VAh±(1%+3dgt)
Phase angle-179°~ 180°±(2°)

Tanφ

(VA≥50VA)

-32.76~ 32.76Min resolution 0.001φ:±(1°)

Phase shift of power factor

(DPF)

-1.000~ 1.0000.001φ:±(1°)

Harmonic ratio

(order 1 to 50) (Vrms>50V)

0.0%~ 99.9%0.1%±(1%+5dgt)

Harmonic angle

(Vrms>50V)

-179°~ 180°±(3°) harmonics of order 1 to 25
±(10°) harmonics of order 26 to 50

Total harmonic ratio

(THD or THD-F)≤50

0.0%~ 99.9%0.1%±(1%+5dgt)

Distortion factor

(DF or THD-R)≤50

0.0%~ 99.9%0.1%±(1%+10dgt)
Transformer K factor1.00~ 99.990.01±(5%)
3 phases unbalance0.0%~ 100%0.1%±(1%)

Current Clamp(optional)

TypeTrue RMS currentMax error of true RMS currentMax error of phase angle
HM-008B current clamp10mA~ 99mA±(1%+3dgt)±(1.5°),Arms≥20mA
100mA~ 10.0A±(1%+3dgt)±(1°)
HM-040B current clamp0.10A~ 0.99A±(1%+3dgt)±(1.5°)
1.00A~ 100A±(1%+3dgt)±(1°)
HM-068B current clamp1.0A~ 9.9A±(2%+3dgt)±(3°)
10.0A~ 1000A±(2%+3dgt)±(2°)
HM-300F Flexible Coil Current Sensor (with Integrator)10A~99A±(1% + 3dgt)±(3°)
100AA~3000A±(1% + 3dgt)±(2°)