| Sign In | Join Free | My chinacomputerparts.com |
|
| Categories | Commercial Air Source Heat Pump |
|---|---|
| Brand Name: | Yushen |
| Model Number: | Commercial Air Source Heat Pump |
| Certification: | CCC, ISO, CQC |
| Place of Origin: | China |
| MOQ: | 1 set |
| Price: | negotiable |
| Payment Terms: | T/T |
| Supply Ability: | 10 sets/day |
| Delivery Time: | 1-2 weeks |
| Packaging Details: | Reinforced Carton box with wooden tray |
| Key word: | Industrial Air Source Heat Pump |
| Compressor capacity: | 12.5HP |
| Advantage: | Low Noise |
| Air blow type: | Side |
| working conditions: | -25C ~+45C |
| Compressor quantity: | 1 |
Low Noise Industrial Air Source Heat Pump , Indoor Air Source Heat Pump -25C ~+45C
Quick Details of Industrial Air Source Heat Pump
Industrial Air Source Heat Pump Applications
Villas
office buildings
hotels and restaurants
Apartments
Industrial Air Source Heat Pump Model data
| Model | SLNB-035Y | |||
| Compressor capacity | 12.5HP | |||
| Function | Heating and Cooling | |||
| Electricity | 380V-3N-50Hz | |||
| Working conditions | ℃ | -25~+45 | ||
| Data | Heata | Nominal capacity | KW | 22.3 |
| Input power | KW | 9.4 | ||
| COP | / | 2.35 | ||
| Heating IPLV(H) | 2.7 | |||
| Coolb | Nominal capacity | KW | 28 | |
| Input power | KW | 10.4 | ||
| COP | / | 2.7 | ||
| Cooling IPLV(C) | 2.7 | |||
| A7W35c | KW/COP | 35.0/4.1 | ||
| A2W35 | KW/COP | 28.5/3.60 | ||
| A-7W35 | KW/COP | 23.5/2.9 | ||
| A-15W55 | KW/COP | 20.2 /1.94 | ||
| A-20W45 | KW/COP | 18.7/2.02 | ||
| Max. running currency | A | 27 | ||
| Compressor quantity | set | 1 | ||
| Refrigerant/charging quantity kg | / | R22/9 | ||
| Air blow type | / | Side | ||
| Water pipe diameter | mm | 32 | ||
| Rating flow | m³/h | 5.9 | ||
| Water side pressure loss | kPa | ≤45 | ||
| Noise level | dB(A) | 62 | ||
| Overall dimensions(L×W×H) | mm | 1490×900×1900 | ||
| Weight | kg | 350 | ||
a: Nominal heating conditions: ambient dry bulb temperature-12℃, wet bulb temperature-14℃, outlet water temperature 41℃, water flow 0.172 * nominal heating capacity
b:Nominal refrigeration conditions: ambient dry bulb temperature 35℃, outlet water temperature 7℃, water flow 0.172 * nominal cooling capacity
c:A7W35 working condition: inlet air temperature 7℃, outlet water temperature 35℃
Industrial Air Source Heat Pump Advantages
Delivery and Packing
Strong and safe packaging for each product so that they will not be any damaged,keeping good the unit performance to users.
|