Sign In | Join Free | My chinacomputerparts.com
chinacomputerparts.com
Products
Search by Category
Home > Cable Manufacturing Equipment >

Live XLPE Cable Partial Discharge Test Equipment , Patrol Type Pd Testing Equipment

Categories Partial Discharge Test Equipment
Brand Name: Fanke High-Voltage
Model Number: PPD8609A
Certification: ISO9001
Place of Origin: China
MOQ: One unit
Price: 15000~25000 USD /Unit
Payment Terms: L/C, T/T
Supply Ability: 10units/month
Delivery Time: 20~25 work days
Packaging Details: Export standard wooden case with fumigation free
Test Principle: High-frequency current sensor (HFCT) measurement and Ultrasonic detecting technology
Usage: Patrol type Partial Discharge Detecting Tester For Live XLPE cable And Power Transformer
Refer standard: GB / T 7354 Partial discharge measurement ;DL/T 417 Guideline for local measurement of partial discharge of electric equipment ;
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

Live XLPE Cable Partial Discharge Test Equipment , Patrol Type Pd Testing Equipment

Patrol type Partial Discharge Detecting Tester For Live XLPE cable And Power Transformer


1. Product introduction:

Due to manufacturing or installation defects, discharge occurs in the insulated portion of the live cable end (joint) until insulation breakdown damage occurs, and even a fire or explosion at uncertain defects may occur. Therefore, how to find the hidden troubles before the accident is the key to solve the problem, which makes the discharge detection necessary for live cable.


The model PPD8209A is a kind of high-frequency partial discharge inspection instrument which adopts the high-frequency current and ultrasonic detection methods for PD inspection and detecting to live MV/HV cable and transformer through HFCT (high-frequency current transformer) or Ultrasonic transducer. It has the feature of small volume, excellent performance and easy operation.


The PD tester adopts modern electronic and computer integrated technology to realize signal amplification (analog, electronic, digital), filtering, data acquisition, data processing, graphic display, test report automatic generation, thus completing the measurement and analysis of partial discharge.


2. Reference Standard

GB 7354 Partial discharge measurement

DLT 417 Guideline for local measurement of partial discharge of electric equipment

GBT 16927.1 High voltage test technology Part 1: General test requirements

GBT 16927.2 High voltage test techniques Part 2: Measuring system

GB T 16927.3 High voltage test techniques Part 3: Definition and requirements of field test


3.Main Components:

SNNameSpecificationsQty
1Patrol type Partial Discharge Detecting TesterPPD8209A1pcs
2Charger for host machine1pcs
3High-frequency current sensorHFCT1pcs
4Ultrasonic sensorJust for live power transformer1pcs
5Cable ultrasonic detectorWith1pcs
6Coaxial cables50Ω2pcs
7Wireless sync transmitters and power cords.1set
8Data storage card reader.1pcs
9signal coupling agentFor Ultrasonic sensor1pcs
10Storage transport case.1pcs

4. Detecting principle and method:

4.1 High-frequency current sensor measurement principle

The high-frequency current sensor is mainly used for partial discharge detection of high-voltage electrical equipment, and adopts the principle of pulse current. Since most high-voltage electrical equipment has distributed capacitance on its high and low voltage side or grounded part, when a high electric field strength area discharge takes place, the discharge signal is coupled to the grounding part and enters the earth through the grounding line. The HFCT sensor is clamped on the ground line and detects the pulse current signal generated by the PD, thereby obtaining partial discharge information of the device during test. It is mainly used for partial discharge signal detection of medium and high voltage equipment such as cables, transformers, reactors, GIS, switch-gear.


4.1.1 High frequency current detection for XLPE Cable

Due to manufacturing or installation defects, discharge occurs in the insulated portion of the cable end joint until insulation breakdown damage occurs, and even a fire or explosion may occur. Therefore, how to find the hidden troubles before the accident is the key to solve the problem, which makes the charge detection necessary.

In high-voltage cables, the wires and the metal sheath shield are separated by an insulating material to form a distributed capacitance, which is about several hundred pF, forming a path for high-frequency signals. Therefore, the high-frequency partial discharge signal is transmitted by the distributed capacitance to the ground lead. When the internal discharge occurs, a high-frequency pulse current is generated, and the high-frequency pulse current flows through the distributed capacitance between the core and the metal sheath , from the high-potential core to the low-level metal shield. On the sleeve , and enter the ground through the cable intermediate connector or the ground wire at the terminal. Therefore, a high-frequency current transformer sensor is connected to the grounding wire at the intermediate joint or terminal to couple the high-frequency pulse partial discharge current into the sensor and pass through the test cable between the sensor and the patrol instrument. The PPD8209A inspection tester performs signal acquisition and analysis.

The indication figure for live cable or live cable joint is as following :


4.2. Ultrasonic (US) measurement principle

When a partial discharge signal is generated inside the power equipment, vibration and sound of the impact are generated. Ultrasonic methods measure partial discharge signals by mounting an ultrasonic sensor on the outer wall of the device chamber. The method is characterized in that the sensor has no connection with the electrical circuit of the geographical equipment, and is not interfered by the electrical appliance, but is susceptible to the surrounding environment noise or the mechanical vibration of outside equipment when used in the field. Since the ultrasonic signal has a large attenuation in the commonly used insulating materials of the power equipment, the detection range of the ultrasonic detecting method is limited, but has the advantage of high PD positioning accuracy.


4.2.2 Ultrasonic detecting PD for live cable

For live high voltage cables, in many cases, due to the poor quality of the cable itself or cable accessories, external force damage and mechanical damage, corrosion and moisture, cable joint construction quality problems, accessories aging and other reasons, the cable joint is prone to partial discharge. Therefore, it is necessary to perform partial discharge detection on high voltage cables.


The PPD8609A tester is a device for detecting a discharge fault of a high voltage cable or cable joint .The detector of the tester adopts an acoustic-electric three-dimensional spatial positioning sensor, and can realize the three-dimensional spatial position and the discharge strength of the discharge point under a condition of not contacting the cable under test. Therefore, the insulation condition of the measured cable point will be judged, and the occurrence of the accident is prevented in advance. This detecting method usually can be applied to on-line detection and positioning of partial discharge of cable ends and cable distribution boxes.


5.General Technical data:

Host machine feature
Number of detecting channels2channels,1 for HFCT method detecting,1 for US method detecting
Sampling accuracy12bit
Trigger modeInternal synchronization and external synchronization
HFCT measuring technical feature
Detection bandwidth100K-50MHz
Transmission impedance>5mV/mA(10MHz )
Output impedance50Ω
Detection sensitivity5pC
Detection range for discharge-20-80dB
Measurement error±1dB
resolution1dB
Signal input interfaceStandard BNC through coaxial cable
Measuring display mode for PD signalWaveform mode, statistical mode,impulse mode
Ultrasound measuring technical feature
Detection frequency range20kHz-300kHz
Output impedance50Ω
Detection sensitivity0.1mV
Detection range for discharge0.1mV~1V
Signal input interfaceStandard BNC through coaxial cable
Measuring display mode for PD signalWaveform mode,continuous mode,phase mode
Hardware of host machine
Display4.3 TF true color LCD screen
Screen resolution480×272
Operation buttonFilm button
Data StorageStandard 16G SD data storage card, 32G can also be supported
Sound input interface3.5mm stereo headphone interface
Charging interfaceDC-005 LV DC charger interface
Charging indicationLED indication light
Other interfaceRS232 Ex-factory commissioning interface
USBD synchronous interface
USB2.0
Network communication port
SD card slot
CH1 HFCT signal interface
US ultrasound signal interface
Supply power
Internal supply16.8V lithium batteries
Normal continuous working timeAbout 7hours, charge time: about 5hour/time
Dimension
L×W×H235mm×133mm×48mm
Weight0.85kg
Using condition
Using ambient temperature-20℃-50℃
Storage ambient temperature-40℃-70℃
Humidity10%-90%,no condensing
Elevationno more than 3000m
China Live XLPE Cable Partial Discharge Test Equipment , Patrol Type Pd Testing Equipment factory
Send your message to this supplier
 
*From:
*To: WUHAN FANKE HAIWO HIGH VOLTAGE TECHNOLOGY CO.,LTD.
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0