Sign In | Join Free | My chinacomputerparts.com |
|
Categories | Low Voltage Switchgear |
---|---|
Brand Name: | TIANAN Electric |
Model Number: | GCT |
Certification: | VDE, CCC, ISO9001:2000 |
Place of Origin: | CHINA |
MOQ: | 1unit |
Price: | US $20,000/ Piece |
Payment Terms: | L/C, D/P, T/T, D/A |
Delivery Time: | 30days |
Packaging Details: | wooden case |
Material: | Type C steel with 25mm modular interval |
shell protection: | IP30 -IP45,IP54(negotiation) |
Altitude: | <=2000m |
Rated insulation voltage: | AC660V |
Rated operating voltage: | AC400 |
Company Info. |
Ningbo Tianan (Group) Co.,Ltd. |
Verified Supplier |
View Contact Details |
Product List |
GCT series LV Drawable Switchgear
GCT Series Low Voltage Drawable Switchgear, a developed product of our company by absorbing the advanced technology of the same type of products in domestic and abroad and improving them, is a newly one which technology has reached to an international leading rank in the world in the 1990s.
This kind of switchgear, with frequency of 50 Hz (AC), rated voltage 660V max, rated current up to 4000A, is widely used in power transmission, distribution and controlling net for power distribution, lighting, motor protection and power supply in power plants, substation works, mining, building, hotel, airport, seaport, etc.
GCT switchgear complying to standard of IEC439 Low-voltage switchgear and Control-gear assemblies and the GB7251 Low-voltage and Control-gear assemblies, had advantage of excellent breaking capacity, good dynamic stability, newly structure, a reasonable and complete electrical scheme, a serial and applicable design and higher protection degree and is a kind of ideal and renew product.
Product Features:
A. Compact, space saving design: More functional units in less
space.
B. High generalization in structure design and flexibility in made
up. The type C sheet with 25mm modular interval can meet all of the
needs of varied kinds of structures, different protection degrees,
operating and environmental conditions.
C. Standard module design: They can make up a variety of standard
units for protection, operating, transferring, controlling,
regulating and indication. The user may choose the relevant
standard units for assembly according to requirements. Up to more
than 200 of structure parts and function modules can make up a
variety of structure frames and drawer unit for different schematic
requirements.
D. Adopting the high strengthen flame-resisting engineering plastic
components, so the reliability and safety protection capacity of
the product has been strengthened.
E. High technical characteristics and the main technical data reach
a high advanced level.
F. Easy installation and disassembly without any special tools.
Rated insulation voltage | AC660V | |
Rated operating voltage | AC400 | |
Max. operating current of main busbar | 4000A (IP30) 6300A | |
Max. operating current of distribution busbar (vertical busbar) | 1250A | |
Horizontal busbar | Short time withstand current | 50kA (rms. 1s) |
Reinforce type | 80kA (rms. 1s) | |
Horizontal busbar | Peak short time withstand current | 105kA (peak) |
Reinforce type | 176kA (peak) | |
Vertical busbar | Short time withstand current | 50kA (rms. )105kA(peak) |
Peak withstand current | 50kA (rms. )105kA(peak) | |
Protection degree | IP30 -IP45,IP54(negotiation) |
![]() |