| Brand Name: | CONSNANT |
| Model Number: | CNG330 |
| Certification: | ICE, ISO |
| Place of Origin: | Shenzhen, China |
| MOQ: | 1 |
| Price: | Negotiable |
| Payment Terms: | T/T, L/C, Western Union |
| Supply Ability: | 200 pieces per month |
| Delivery Time: | 21 days |
| Packaging Details: | Export Standard Package |
| Inpur voltage: | 400 Vac three-phase ±20% |
| Input Frequency range: | 45-65Hz |
| Input Current harmonic distortion: | <5%with harmonic filter |
| Bypass voltage range: | 400Vac single-phase ±15%(selectable from ±10% to ±25% from front panel) |
| Permitted frequency range: | ±2%(selectable from ±1% to ±5% from front panel) |
| Inverter Number of phases: | 3+N |
| Efficiency smart mode: | up to 98% |
Three Phase UPS Uninterrupted Power Supply Low Frequency Online UPS 10-200KVA
CNG330 Series Low Frequency Online UPS 10-200KVA
Model:CNG330 10-200KVA(3Ph/3Ph)
Nominal Input Voltage: 380/400/415VAC
Output Power Factor:0.8
Crest factor (Ipeak / Irms): 3:1
Rated frequency: 50/60Hz
Application:
Servers,
Local area Network(LAN),
Data centers,
Telecommunications,
Electro-medical equipment
Specification:
| Model power | CNG330 10-200KVA | |||||||||||
| 10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA | 100KVA | 120KVA | 160KVA | 200KVA | ||
| Capacity | 8KW | 12 KW | 16 KW | 24 KW | 32 KW | 48 KW | 64 KW | 80 KW | 96KW | 128 KW | 160 KW | |
| Input | ||||||||||||
| Rated voltage | 400 Vac three-phase | |||||||||||
| Voltage range | ±20% | |||||||||||
| Frequency range | 45-65Hz | |||||||||||
| Power factor | >0.92with harmonic filter | |||||||||||
| Current harmonic distortion | <5%with harmonic filter | |||||||||||
| Soft Start | 0-100% in10" | |||||||||||
| Bypass Input | ||||||||||||
| Rated voltage | 400Vac single-phase | |||||||||||
| Permitted voltage range | ±15%(selectable from ±10% to ±25% from front panel) | |||||||||||
| Permitted frequency range | ±2%(selectable from ±1% to ±5% from front panel) | |||||||||||
| Standard features | Back Feed protection; split bypass line | |||||||||||
| Batteries | ||||||||||||
| Type | Maintenance-free lead-acid VRLA AGM / GEL;NICd | |||||||||||
| Battery voltage | 384VDC | 480VDC | ||||||||||
| Maximum recharge current(A) | 0.2×C10 | |||||||||||
| AC ripple voltage | <1% | |||||||||||
| Inverter Output | ||||||||||||
| Number of phases | 3+N | |||||||||||
| Rated voltage(V) | 400Vac | |||||||||||
| Regulation of the output voltage | 380~424Vac phase/neutral(from control panel) | |||||||||||
| Static stability | ±1% | |||||||||||
| Dynamic stability | ±5% | |||||||||||
| Frequency | 50/60Hz configurable | |||||||||||
| Overload | 110% 125% 150% of the rated current for 5h/10'/1' | |||||||||||
| Frequency stability | ±0.05% on mains failure;±2%(selectable from ±1% to ±5%)with mains supply present | |||||||||||
| Remote signaling | Volt free contacts | |||||||||||
High intelligence and reliable power supply:
Maximum battery care:
Simple to install:
High reliability:
Back feed protection:
To avoid energy feeding back into the mains supply cause a fault
occur.
Maximum reliability and availability:
Connect up to 6 units in parallel or N+1 redundancy, even of
different power ratings.The UPS continue to work in parallel even
if one of the interconnecting communication cables is disconnected
(CLOOSED LOOP).
Advance communication:
Expandability:
Other characteristics:


|